| Product Name | 120W/48V Industrial DIN Rail Power Supply | 120W/24V Industrial DIN Rail Power Supply |
| Model | DP120-48 | DP120-24 |
| Group of Output | 1 | 1 |
| DC Voltage | 48V | 24V |
| Default Output Voltage | 48.00-48.2V (Vin: 220VAC / LOAD: 0A) | 24.00-24.2V (Vin: 220VAC / LOAD: 0A) |
| Output Rated Current | 2.5A | 5A |
| Output Current Range | 0-2.5A | 0-5A |
| Output Rated Power | 120W | 120W |
| Total Peak Output Power | Up to 180W(Sustainable time 10S/220VAC) | Up to 180W(Sustainable time 10S/220VAC) |
| Peak Output Current | 3.5A( Sustainable time 10S/220VAC) | 7.5A( Sustainable time 10S/220VAC) |
| Ripple noise | Peak - Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) | Peak - Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) |
| Output Regulation Range @25℃ | 46~56V | 22.5~28V |
| Stabilized Voltage Precision | ±1% (@ 90-264Vac input, 100% load) | ±1% (@ 90-264Vac input, 100% load) |
| Line Regulation | ±0.5% (@ 90-264Vac input, 100% load) | ±0.5% (@ 90-264Vac input, 100% load) |
| Load Regulation | ±1% (@ 90-264Vac input, 100% load) | ±1% (@ 90-264Vac input, 100% load) |
| Temperature Coefficient | ±0.03%/℃ | ±0.03%/℃ |
| Output Start Time | < 2S @ nominal input (100% load ) | < 1S @ nominal input (100% load ) |
| Output Hold Time | > 20ms @ 115Vac, > 50 ms @ 230Vac (100% load ) | > 20ms @ 115Vac, > 115 ms @ 230Vac (100% load ) |
| Voltage Overshoot | ≤5% | ≤5% |
| Input Voltage Range | 90~264VAC | 90~264VAC |
| Input Rated Voltage Range | 100~240VAC | 100~240VAC |
| Frequency Range | 47Hz~63Hz | 47Hz~63Hz |
| Starting Voltage | 90Vac | 90Vac |
| Efficiency | > 90.0% @ 115Vac, > 91.0% @ 230Vac | > 90.0% @ 115Vac, > 91.0% @ 230Vac |
| Input Current | < 2.20A @ 115Vac, < 1.10A @ 230Vac | < 2.20A @ 115Vac, < 1.10A @ 230Vac |
| Inrush Starting Current | < 35A @ 115Vac & 230Vac | < 35A @ 115Vac & 230Vac |
| Power Factor @25℃ | > 0.99 @ 115Vac, > 0.93 @ 230Vac | > 0.99 @ 115Vac, > 0.93 @ 230Vac |
| Over Power Protection | 144~180W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-power released. | 144~180W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-power released. |
| Over Voltage Protection | 57~70V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit) Note: Do not use external voltage. | 30~36V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit) Note: Do not use external voltage. |
| Over Current | 3~3.75A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-current released.) | 6~7.5A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-current released.) |
| Short Circuit Protection | It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with power output port. Self-recovery to normal after removing the short circuit. | It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with power output port. Self-recovery to normal after removing the short circuit. |
| Operation Temperature and Humidity | -40~70℃; 20%~95%RH | -40~70℃; 20%~95%RH |
| Storage Temperature and Humidity | -40℃~85℃; 10%~95%RH non-condensing | -40℃~85℃; 10%~95%RH non-condensing |
| Libration | Frequency range: 10 ~ 500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axis | Frequency range: 10 ~ 500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axis |
| Surge | Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y and Z axis | Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y and Z axis |
| Altitude | 2000m | 2000m |
| Security Standard | GB4943/EN60950 ■Reference □Certification | GB4943/EN60950 ■Reference □Certification |
| Dielectric Strength | Input—Output:3KVac/10mA; Input--Case:1.5KVac/10mA; Output---Case:0.5KVDC/10mA Time for each testing is 1min. | Input—Output:3KVac/10mA; Input--Case:1.5KVac/10mA; Output---Case:0.5KVDC/10mA Time for each testing is 1min. |
| Grounding Test | Test Condition: 32A/2min; Ground bond: <0.1 ohms. | Test Condition: 32A/2min; Ground bond: <0.1 ohms. |
| Leakage Current | Input to GND ≤3.5mA; Input to output ≤0.25mA (Input 264Vac, 63Hz) | Input to GND ≤3.5mA; Input to output ≤0.25mA (Input 264Vac, 63Hz) |
| Insulation Resistance | Input—Output: 10M ohms; | Input—Output: 10M ohms; |
| Conducted Interference | EN55022, EN55024, FCC PART 15 CLASS B | EN55022, EN55024, FCC PART 15 CLASS B |
| Radiated Interference | EN55022, EN55024, FCC PART 15 CLASS B | EN55022, EN55024, FCC PART 15 CLASS B |
| Harmaonic current | EN61000-3-2 CLASS D | EN61000-3-2 CLASS D |
| Conducted Emission | EN61000-4-6 Level3 | EN61000-4-6 Level3 |
| Radiated Emission | EN61000-4-3 Leve3 criterion B | EN61000-4-3 Leve3 criterion B |
| Power Frequency Emission | EN61000-4-8 Level3 | EN61000-4-8 Level3 |
| Electrostatic Emission | EN61000-4-2 Level4 criterion B | EN61000-4-2 Level4 criterion B |
| EFT | EN61000-4-4 Level4 criterion B | EN61000-4-4 Level4 criterion B |
| Surge | EN61000-4-5 Level4 criterion B | EN61000-4-5 Level4 criterion B |
| Dip and Interruption | EN61000-4-11 | EN61000-4-11 |
| Dimension/Weight | 134*124*41mm / 580g | 134*124*41mm / 580g |